Digital Process Monitor DPM52A
DPM52A features
DPM52A applications
DPM52A technical parameters
Parameter | min | nom | max | unit | note |
Input range | 0 - 20 | mA | |
Displayed range | -32 768 | | 32 767 | |
Measuring error | | | 0,3 | % |
Thermal stability | | | 15 | ppm |
Long term stability | | | 50 | ppm/1000h |
Voltage drop on measuring terminals | | | 350 | mV | at 20 mA |
Maximum measuring terminals current | | | 300 | mA | |
Analog inputs | 2 | |
Relay outputs | 2 | |
Relay outputs form | 1C | |
Relay output current rating (resistive load) | | | 6 | A | AC |
Relay output voltage rating | | | 250 | V | AC |
Samples averaging time (damping) | 0,12 | | 15 | s | parameter |
Number of averaged samples | 1 | | 125 | | parameter |
Limit adjustment range | -32 768 | | 32 767 | | parameter |
Hysteresis adjustment range | 0 | | 32 767 | | parameter |
Power supply voltage | 18 | 24 | 30 | V | |
Power supply current | 105 | mA | at 24 V |
Conductor cross-section for terminals | 0,08 | | 2,5 | mm2 | |
Dimensions (width x height x depth) | 96 x 48 x 146 | mm |
Weight | 250 | g |
Operating ambient temperature | -25 | | 60 | °C |
Storage ambient temperature | -45 | | 85 | °C |
Protection | IP20 | |
Download